Appendix B -Settings and Signals
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
Programmable
Selection of the generic scheme type for aided channel 1.
Note: POR is equivalent to POTT (permissive overreach transfer trip), PUR is
equivalent to PUTT (permissive underreach transfer trip).
Aid 1 Distance 34 42 Phase And Ground
Phase only
Ground only
Phase And Ground
Setting to select whether distance elements should key the scheme selected as per the previous setting. If set to Disabled, no distance zones
interact with this aided scheme, and basic scheme tripping only applies.
Aid.1 Dist. Dly 34 43 0
From 0 to 1 in steps of 0.002
[Courier Number (time-seconds)]
Trip time delay for Aided 1 Distance schemes.
Aid. 1 DEF 34 44 Disabled
Enabled
Setting to select whether a DEF scheme should be mapped to Aided scheme 1.
(Not applicable where a Permissive Underreaching scheme selection has been made).
Aid. 1 DEF Dly. 34 45 0
From 0 to 1 in steps of 0.002
[Courier Number (time-seconds)]
Time delay for Aided 1 DEF tripping.
Aid. 1 DEF Trip 34 46 3 Pole
1 and 3 Pole
Setting that defines the tripping mode for Aided 1 DEF.
This setting is visible only if tripping mode under GROUP x LINE PARAMETERS/Trip Mode is set to 1 and 3 pole.
Aid. 1 Delta 34 47 Disabled
Enabled
Setting to select whether a Delta directional comparison scheme should be mapped to Aided scheme 1.
(Not applicable where a Permissive Underreaching scheme selection has been made).
Aid. 1 Delta Dly 34 48 0
From 0 to 1 in steps of 0.002
[Courier Number (time-seconds)]
Time delay for Aided 1 Delta tripping.
Aid. 1 DeltaTrip 34 49 3 Pole
1 and 3 Pole
Setting that defines tripping mode for Aided 1 Delta.
This setting is visible only if tripping mode under GROUP x LINE PARAMETERS/ Trip Mode is set to 1 and 3 pole.
tReversal Guard 34 4A 0.02
From 0 to 0.15 in steps of 0.002
[Courier Number (time-seconds)]
Setting for the current reversal guard timer. Intended to keep stability on a healthy line, whilst breakers open on a faulted parallel line to
clear the fault.
This setting is visible only when over-reaching or Blocking schemes are selected.
Unblocking Delay 34 4B 0.05
From 0 to 0.1 in steps of 0.002
[Courier Number (time-seconds)]
Time delay after Loss of Guard until unblocking occurs. After the set delay, the relay will respond as though an aided signal has been
received from the remote end.
This setting is visible only when PUR Unblocking, POR Unblocking or Programmable Unblocking schemes are chosen.
Send on Trip 34 4C Aided / Z1
Any Trip
None
Setting that defines the reinforced trip signal for POR Aided 1 scheme.
If selected to: None: No reinforced signal is issued
Aided/Z1: The reinforced signal is issued with aided trip or with Z1 if aided distance scheme is enabled
Any Trip: Signal is reinforced with Any trip (DDB 522)