Appendix B -Settings and Signals 
 
 
 
MENU TEXT  COL  ROW  DEFAULT SETTING  AVAILABLE OPTIONS 
DESCRIPTION 
IEEE V Inverse 
IEEE E Inverse 
US Inverse 
US ST Inverse 
IDG 
Setting for the tripping characteristic for the first stage earth fault overcurrent element. 
IN>1 Direction  38  26  Non-Directional 
Directional Fwd 
Directional Rev 
This setting determines the direction of measurement for first stage element. 
IN>1 Current Set  38  29  0.2 
From 0.08*I1 to 4.0*I1 in steps of 0.01*I1 
[Courier Number (current)] 
Pick-up setting for first stage overcurrent element 
IN1>1 IDG Is  38  2A  1.5 
From 1 to 4 in steps of 0.1 
[Courier Number (decimal)] 
This setting is set as a multiple of “IN>” setting for the IDG curve (Scandinavian) and determines the actual relay current threshold at which 
the element starts. 
IN>1 Time Delay  38  2C  1 
From 0 to 200 in steps of 0.01 
[Courier Number (time-seconds)] 
Setting for the time-delay for the definite time setting if selected for first stage element. The setting is available only when DT function is 
selected. 
IN>1 TMS  38  2D  1 
From 0.025 to 1.2 in steps of 0.005 
[Courier Number (decimal)] 
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic. 
IN>1 Time Dial  38  2E  1 
From 0.01 to 100 in steps of 0.01 
[Courier Number (decimal)] 
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves. The Time Dial (TD) is a multiplier on the 
standard curve equation, in order to achieve the required tripping time. The reference curve is based on TD = 1.  
Care: Certain manufacturer's use a mid-range value of TD = 5 or 7, so it may be     necessary to divide by 5 or 7 to achieve parity. 
IN1>1 IDG Time  38  30  1.2 
From 1 to 2 in steps of 0.01 
[Courier Number (time-seconds)] 
Setting for the IDG curve used to set the minimum operating time at high levels of fault current. 
IN>1 Reset Char  38  32  DT 
Inverse 
Setting to determine the type of reset/release characteristic of the IEEE/US curves. 
IN>1 tRESET  38  33  0 
From 0 to 100 in steps of 0.01 
[Courier Number (time-seconds)] 
Setting that determines the reset/release time for definite time reset characteristic. 
IN>2 Status  38  35  Disabled 
Enabled 
Enabled VTS 
Enabled Ch Fail 
En VTSorCh Fail 
En VTSandCh Fail 
Setting that defines secondstage overcurrent operating status. Depending of this setting, IN>2 will be enabled permanently or in case of 
Voltage Transformer Supervision (fuse fail) operation, or in case of communication channel fail, or a combination (and /or) of both. 
IN>2 Function  38  36  IEC S Inverse 
IEC S Inverse 
IEC V Inverse 
IEC E Inverse 
UK LT Inverse 
IEEE M Inverse 
IEEE V Inverse 
IEEE E Inverse 
US Inverse