EasyManua.ls Logo

GE MiCOM P40 - Page 862

GE MiCOM P40
962 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix B -Settings and Signals
P446SV
B116
P446SV-TM-EN-1
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
IDG
[Indexed String]
Setting for the tripping characteristic for the second stage earth fault overcurrent element.
IN>2 Direction 38 37 Non-Directional
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
This setting determines the direction of measurement for first stage element.
IN>2 Current Set 38 3A 0.2
From 0.08*I1 to 4.0*I1 in steps of 0.01*I1
[Courier Number (current)]
Pick-up setting for second stage overcurrent element
IN2>1 IDG Is 38 3B 1.5
From 1 to 4 in steps of 0.1
[Courier Number (decimal)]
This setting is set as a multiple of “IN>” setting for the IDG curve (Scandinavian) and determines the actual relay current threshold at which
the element starts.
IN>2 Time Delay 38 3D 1
From 0 to 200 in steps of 0.01
[Courier Number (time-seconds)]
Setting for the time-delay for the definite time setting if selected for second stage element. The setting is available only when DT function is
selected.
IN>2 TMS 38 3E 1
From 0.025 to 1.2 in steps of 0.005
[Courier Number (decimal)]
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic.
IN>2 Time Dial 38 3F 1
From 0.01 to 100 in steps of 0.01
[Courier Number (decimal)]
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves. The Time Dial (TD) is a multiplier on the
standard curve equation, in order to achieve the required tripping time. The reference curve is based on TD = 1.
Care: Certain manufacturer's use a mid-range value of TD = 5 or 7, so it may be necessary to divide by 5 or 7 to achieve parity.
IN2>1 IDG Time 38 41 1.2
From 1 to 2 in steps of 0.01
[Courier Number (time-seconds)]
Setting for the IDG curve used to set the minimum operating time at high levels of fault current.
IN>2 Reset Char 38 43 DT
DT
Inverse
[Indexed String]
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
IN>2 tRESET 38 44 0
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting that determines the reset/release time for definite time reset characteristic.
IN>3 Status 38 46 Disabled
Disabled
Enabled
Enabled VTS
Enabled Ch Fail
En VTSorCh Fail
En VTSandCh Fail
[Indexed String]
Setting that defines third stage overcurrent operating status. Depending of this setting, IN>3 will be enabled permanently or in case of
Voltage Transformer Supervision (fuse fail) operation, or in case of communication channel fail, or a combination (and /or) of both.
IN>3 Direction 38 47 Directional Fwd
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
This setting determines the direction of measurement for the earth fault overcurrent element.
IN>3 Current Set 38 4A 10
From 0.08*I1 to 32*I1 in steps of 0.01*I1
[Courier Number (current)]
Pick-up setting for third stage earth fault overcurrent element.
IN>3 Time Delay 38 4B 0
From 0 to 200 in steps of 0.01
[Courier Number (time-seconds)]
Setting for the operating time-delay for third stage earth fault overcurrent element.
IN>4 Status 38 4D Disabled
Disabled
Enabled
Enabled VTS

Table of Contents

Related product manuals