P446SV
Appendix B -Settings and Signals
P446SV-TM-EN-1
B127
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
[Courier Number (voltage)]
This setting determines the pick-up setting for the second stage overvoltage element.
V1>2 Cmp Tim Dly 42 29 0.5
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting for the operating time-delay for the second stage definite time compensated overvoltage element.
GROUP 1: FREQ
PROTECTION
43 00
This column contains settings for Frequency
UNDER FREQUENCY
43
01
F<1 Status 43 02 Enabled
Disabled
Enabled
[Indexed String]
Setting to enable or disable the first stage underfrequency element.
F<1 Setting 43 03 49.5
From 45 to 65 in steps of 0.01
[Courier Number (frequency)]
Setting that determines the pick-up threshold for the first stage underfrequency element.
F<1 Time Delay 43 04 4
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting that determines the minimum operating time-delay for the first stage underfrequency element.
F<2 Status 43 05 Disabled
Disabled
Enabled
[Indexed String]
Setting to enable or disable the second stage underfrequency element.
F<2 Setting 43 06 49
From 45 to 65 in steps of 0.01
[Courier Number (frequency)]
Setting that determines the pick-up threshold for the second stage underfrequency element.
F<2 Time Delay 43 07 3
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting that determines the minimum operating time-delay for the second stage underfrequency element.
F<3 Status 43 08 Disabled
Disabled
Enabled
[Indexed String]
Setting to enable or disable the third stage underfrequency element.
F<3 Setting 43 09 48.5
From 45 to 65 in steps of 0.01
[Courier Number (frequency)]
Setting that determines the pick-up threshold for the third stage underfrequency element.
F<3 Time Delay 43 0A 2
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting that determines the minimum operating time-delay for the third stage underfrequency element.
F<4 Status 43 0B Disabled
Disabled
Enabled
[Indexed String]
Setting to enable or disable the fourth stage underfrequency element.
F<4 Setting 43 0C 48
From 45 to 65 in steps of 0.01
[Courier Number (frequency)]
Setting that determines the pick-up threshold for the fourth stage underfrequency element.
F<4 Time Delay 43 0D 1
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting that determines the minimum operating time-delay for the fourth stage underfrequency element.
F< Function Link 43 0E 0x0
F<1 U/V Block
F<2 U/V Block
F<3 U/V Block
F<4 U/V Block
[Binary Flag (4 bits)]
Settings that determines whether undervoltage level (setting CB FAIL & P.DEAD/POLEDEAD VOLTAGE/V< ) signal block the underfrequency
elements.
OVER FREQUENCY
43
0F
F>1 Status
43
10
Enabled
Disabled

Table of Contents