Appendix B -Settings and Signals
P446SV
B128
P446SV-TM-EN-1
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
Enabled
[Indexed String]
Setting to enable or disable the first stage overfrequency element.
F>1 Setting 43 11 50.5
From 45 to 65 in steps of 0.01
[Courier Number (frequency)]
Setting that determines the pick-up threshold for the first stage overfrequency element.
F>1 Time Delay 43 12 2
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting that determines the minimum operating time-delay for the first stage overfrequency element.
F>2 Status 43 13 Disabled
Disabled
Enabled
[Indexed String]
Setting to enable or disable the second stage overfrequency element.
F>2 Setting 43 14 51
From 45 to 65 in steps of 0.01
[Courier Number (frequency)]
Setting that determines the pick-up threshold for the second stage overfrequency element.
F>2 Time Delay 43 15 1
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting that determines the minimum operating time-delay for the second stage overfrequency element.
GROUP 1: DF/DT
PROTECTION
44 00
This column contains settings for rate of change of Frequency
df/dt Avg.Cycles 44 01 6
6 or 12
[Unsigned Integer (16 bits)]
This setting is available for calculating the rate of change of frequency measurement over a fixed period of either 6 or 12 cycles.
df/dt>1 Status 44 04 Enabled
Disabled
Enabled
[Indexed String]
Setting to enable or disable the first stage df/dt element.
df/dt>1 Setting 44 05 2
From 0.1 to 10 in steps of 0.1
[Courier Number (Hz/sec)]
Pick-up setting for the first stage df/dt element.
df/dt>1 Dir'n 44 06 Negative
Negative
Positive
Both
[Indexed String]
This setting determines whether the element will react to rising or falling frequency conditions respectively, with an incorrect setting being
indicated if the threshold is set to zero.
df/dt>1 Time 44 07 0.5
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Minimum operating time-delay setting for the first stage df/dt element.
df/dt>2 Status 44 0B Enabled
Disabled
Enabled
[Indexed String]
Setting to enable or disable the second stage df/dt element.
df/dt>2 Setting 44 0C 2
From 0.1 to 10 in steps of 0.1
[Courier Number (Hz/sec)]
Pick-up setting for the second stage df/dt element.
df/dt>2 Dir'n 44 0D Negative
Negative
Positive
Both
[Indexed String]
This setting determines whether the element will react to rising or falling frequency conditions respectively, with an incorrect setting being
indicated if the threshold is set to zero.
df/dt>2 Time 44 0E 1
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Minimum operating time-delay setting for the second stage df/dt element.
df/dt>3 Status 44 12 Enabled
Disabled
Enabled
[Indexed String]