Appendix B -Settings and Signals 
 
 
 
MENU TEXT  COL  ROW  DEFAULT SETTING  AVAILABLE OPTIONS 
DESCRIPTION 
Setting to enable or disable the third stage df/dt element. 
df/dt>3 Setting  44  13  2 
From 0.1 to 10 in steps of 0.1 
[Courier Number (Hz/sec)] 
Pick-up setting for the third stage df/dt element. 
df/dt>3 Dir'n  44  14  Negative 
Positive 
Both 
This setting determines whether the element will react to rising or falling frequency conditions respectively, with an incorrect setting being 
indicated if the threshold is set to zero. 
df/dt>3 Time  44  15  2 
From 0 to 100 in steps of 0.01 
[Courier Number (time-seconds)] 
Minimum operating time-delay setting for the third stage df/dt element. 
df/dt>4 Status  44  19  Enabled 
Enabled 
Setting to enable or disable the fourth stage df/dt element. 
df/dt>4 Setting  44  1A  2 
From 0.1 to 10 in steps of 0.1 
[Courier Number (Hz/sec)] 
Pick-up setting for the fourth stage df/dt element. 
df/dt>4 Dir'n  44  1B  Negative 
Positive 
Both 
This setting determines whether the element will react to rising or falling frequency conditions respectively, with an incorrect setting being 
indicated if the threshold is set to zero. 
df/dt>4 Time  44  1C  3 
From 0 to 100 in steps of 0.01 
[Courier Number (time-seconds)] 
Minimum operating time-delay setting for the fourth stage df/dt element. 
CB Fail 1 Status  45  02  Enabled 
Enabled 
Setting to enable or disable the first stage of the circuit breaker function. 
CB Fail 1 Timer  45  03  0.2 
From 0 to 10 in steps of 0.01 
[Courier Number (time-seconds)] 
Setting for the circuit breaker fail timer stage 1, during which breaker opening must be detected.  There are timers per phase to cope with 
evolving faults, but the timer setting is common. 
CB Fail 2 Status  45  04  Disabled 
Enabled 
Setting to enable or disable the second stage of the circuit breaker function. 
CB Fail 2 Timer  45  05  0.4 
From 0 to 10 in steps of 0.01 
[Courier Number (time-seconds)] 
Setting for the circuit breaker fail timer stage 2, during which breaker opening must be detected. 
Volt Prot Reset  45  06  Prot Reset & I< 
CB Open & I< 
Prot Reset & I< 
Setting which determines the elements that will reset the circuit breaker fail time for voltage protection function initiated circuit breaker fail 
conditions. 
Ext Prot Reset  45  07  Prot Reset & I< 
CB Open & I< 
Prot Reset & I< 
Setting which determines the elements that will reset the circuit breaker fail time for external protection function initiated circuit breaker fail 
conditions. 
WI Prot Reset  45  08  Disabled