Appendix B -Settings and Signals
P446SV
B140
P446SV-TM-EN-1
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
CB1L SC all 49 A6 Disabled
Disabled
Enabled
[Indexed String]
This setting determines whether a system check (e.g. live bus / dead line etc) is required for any auto-reclose of CB1 as leader. If Enabled,
system check is required for some or all reclosures. If Disabled, system check is not required for any reclosures.
CB1L SC Shot 1 49 A7 Disabled
Disabled
Enabled
[Indexed String]
This setting determines whether a system check (e.g. live bus / dead line etc) is required for the first shot reclosure of CB1 as leader. If
Enabled, system check is required for the first shot reclosure. If Disabled, system check is not required for the first shot reclosure.
CB1L SC ClsNoDly 49 A8 Disabled
Disabled
Enabled
[Indexed String]
If CB1L SC ClsNoDly is Enabled, CB1 can reclose as leader as soon as the synchro check conditions are satisfied, without waiting for the dead
time to elapse.
This option is sometimes required for the second line end to reclose onto a line with delayed auto-reclosing (typical cycle: first line end
recloses after the dead time with
live bus & dead line, then the second line end recloses immediately with live bus & live line in synchronism).
CB1L SC CS1 49 A9 Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB1 to auto-reclose as leader when the system satisfies all the System Check Synchronism Stage 1 criteria as defined
under CB1 CS1 Status settings in the SYSTEM CHECKS column.
CB1L SC CS2 49 AA Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB1 to auto-reclose as leader when the system satisfies all the System Check Synchronism Stage 2 criteria as defined
under the setting CB1 CS2 status in the SYSTEM CHECKS column.
CB1L SC DLLB 49 AB Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB1 to auto-reclose as leader when the dead line & live bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB1L SC LLDB 49 AC Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB1 to auto-reclose as leader when the live line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB1L SC DLDB 49 AD Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB1 to auto-reclose as leader when the dead line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2L SC all 49 AE Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB1 to auto-reclose as leader when the dead line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2L SC Shot 1 49 AF Disabled
Disabled
Enabled
[Indexed String]
This setting determines whether a system check (e.g. live bus / dead line etc) is required for the first shot reclosure of CB2 as leader. If
Enabled, system check is required for the first shot reclosure. If Disabled, system check is not required for the first shot reclosure.
CB2L SC ClsNoDly 49 B0 Disabled
Disabled
Enabled
[Indexed String]
If CB2L SC ClsNoDly is Enabled, CB2 can reclose as leader as soon as the synchro check conditions are satisfied, without waiting for the dead
time to elapse.
This option is sometimes required for the second line end to reclose on a line with delayed auto-reclosing (typical cycle: the first line end
recloses after the dead time with live bus & dead line, then the second line end recloses immediately with live bus & live line in synchronism).
CB2L SC CS1
49
B1
Disabled
Disabled