Appendix B -Settings and Signals
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
system check is required for some or all reclosures. If Disabled, system check is not required for any reclosures.
CB2F SC Shot 1 49 BE Disabled
Enabled
This setting determines whether a system check (e.g. live bus / dead line etc) is required for the first shot reclosure of CB2 as follower. If
Enabled, system check is required for the first shot reclosure. If Disabled, system check is not required for the first shot reclosure.
CB2F SC CS1 49 BF Disabled
Enabled
This setting enables CB2 to auto-reclose as follower when the system satisfies all the System Check Synchronism Stage 1 conditions as listed
under setting CB2 CS1 Status in the SYSTEM CHECKS column.
CB2F SC CS2 49 C0 Disabled
Enabled
This setting enables CB2 to auto-reclose as follower when system satisfies all the System Check Synchronism Stage 2 conditions as listed
under setting CB2 CS2 Status in the SYSTEM CHECKS settings.
CB2F SC DLLB 49 C1 Disabled
Enabled
This setting enables CB2 to auto-reclose as follower when the dead line & live bus 2 conditions are satisfied in the SYSTEM CHECKS column.
CB2F SC LLDB 49 C2 Disabled
Enabled
This setting enables CB2 to auto-reclose as follower when the live line & dead bus 2 conditions are satisfied in the SYSTEM CHECKS column.
CB2F SC DLDB 49 C3 Disabled
Enabled
This setting enables CB2 to auto-reclose as follower when the dead line & dead bus 2 conditions are satisfied in the SYSTEM CHECKS settings.
4A 00
This column contains settings for Input Labels
Opto Input 1 4A 01 Input L1
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]
Opto Input 2 4A 02 Input L2
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]
Opto Input 3 4A 03 Input L3
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]
Opto Input 4 4A 04 Input L4
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]
Opto Input 5 4A 05 Input L5
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]
Opto Input 6 4A 06 Input L6
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]
Opto Input 7 4A 07 Input L7
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]
Opto Input 8 4A 08 Input L8
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]
Opto Input 9 4A 09 Input L9
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]
Opto Input 10 4A 0A Input L0A
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]