Chapter 3. CPU Configuration
GFK-2222AD April 2018 115
3.2.3 SNTP
This tab displays the Simple Network Time Protocol configuration settings when SNTP is active.
SNTP Mode
SNTP Mode of operation. Specify the use of Multicast/Broadcast or Unicast settings to
communicate to the time server.
Choices: Multicast/Broadcast or Unicast.
Default: Multicast/Broadcast.
Poll Interval
Interval, in seconds, at which new time requests are sent to the server. Only available when
SNTP Mode is set to Unicast.
Valid Range: 16 to 1024, even values only.
Default: 32.
Primary IP
Address
IP address of the primary time server in dotted decimal format.
Valid Range: Any valid unicast IPv4 address.
Default: 0.0.0.0.
Secondary IP
Address
Optional IP address of the secondary time server in dotted decimal format.
Valid Range: Any valid unicast IPv4 address or 0.0.0.0 if unused.
Default: 0.0.0.0.
Poll Count
Number of retransmissions that will be sent when no timely response is received from the
server.
Valid Range: 1 to 100.
Default: 3.
Poll Timeout
The time, in seconds, to wait for a response from the server.
Valid Range: 1 to 100.
Default: 2.

Table of Contents

Other manuals for GE PACSystems RX7i

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE PACSystems RX7i and is the answer not in the manual?

GE PACSystems RX7i Specifications

General IconGeneral
BrandGE
ModelPACSystems RX7i
CategoryController
LanguageEnglish

Related product manuals