EasyManuals Logo

GE PACSystems RX7i Reference Manual

GE PACSystems RX7i
317 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #215 background imageLoading...
Page #215 background image
Chapter 6. Serial I/O, SNP & RTU Protocols
204 PACSystems* RX7i, RX3i and RSTi-EP CPU Reference Manual GFK-2222AD
6.1.5 COMMREQ Command Block Parameter Values
The following table lists common parameter values that are used within the COMMREQ command blocks
for configuring a serial port. All values are in decimal.
Parameter
Values
Protocol Selector
1 = SNP
3 = RTU
5 = Serial I/O
7 = Message Mode
Data Rate
0 = 300
1 = 600
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 19200
7 = 38400
8 = 57600
9 = 115200
Parity
0 = None
1 = Odd
2 = Even
Flow Control
0 = Hardware [RTS / CTS]
1 = None
2 = Software [XON / XOFF] (Serial I/O only)
Bits Per Character
0 = 7 bits
1 = 8 bits
Stop Bits
0 = 1 stop bit
1 = 2 stop bits
Duplex Mode
0 = 2-wire
1 = 4-wire
2 = 4-wire transmitter always on
Turnaround Delay (SNP only)
0 = none
1 = 10ms
2 = 100ms
3 = 500ms
Timeout (SNP only)
0 = Long (8 sec)
1 = Medium (2 sec)
2 = Short (500ms)
3 = None (200ms)

Table of Contents

Other manuals for GE PACSystems RX7i

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE PACSystems RX7i and is the answer not in the manual?

GE PACSystems RX7i Specifications

General IconGeneral
BrandGE
ModelPACSystems RX7i
CategoryController
LanguageEnglish

Related product manuals