Chapter 2. CPU Features & Specifications
GFK-2222AD April 2018 29
2.2 RX3i CPU Features and Specifications
CPU310
CPU315
CPU320/
CRU320
17
CPE302
18
/
CPE305
CPE310
CPE330
CPE400
Lifecycle Phase
Discontinued -
use CPE310
Discontinued -
use CPE310
or CPE330
Discontinued -
use CPE330
Active
Active
Active
Active
Microprocessor Specification
300 MHz Intel
Celeron
1 GHz Intel
Celeron M
1 GHz Intel
Celeron M
1.1 GHz Intel
Z510PT
Silverthorne XL
“Atom”
1.1 GHz Intel
Z510PT
Silverthorne XL
“Atom”
1 GHz AMD
G-Series Dual
Core SoC
GX-209HA
1.2 GHz AMD
G-Series Quad
Core SoC GX-
216HC
Operating System
VxWorks
VxWorks
VxWorks
VxWorks
VxWorks
VxWorks
VxWorks
#RX3i Slots Occupied
2
2
2
1
2
2
N/A
Backplane
<----------------------Supports High-Speed PCI IC695* and Serial IC694* Modules -------------------------->
Field Agent
Temperature Range
RX3i
0°C to 60°C
0°C to 60°C
0°C to 60°C
0°C to 60°C
19
0°C to 60°C
15
0°C to 60°C
-40°C to 70°C
20
Power Requirements
RX3i +3.3Vdc
1.25 A
1.0 A
1.0 A
1.0 A
1.0 A
0 A
N/A
RX3i +5 Vdc
1.0 A
1.2 A
1.2 A
1.0 A
(up to 1.5 A if
USB draws 0.5A)
1.0 A
(up to 1.5 A if
USB draws 0.5A)
0 A
N/A
RX3i +24Vdc Relay with Energy Pack
0.5 A at start-up;
0.1 A otherwise
0.5 A at start-up;
0.1 A otherwise
0.750 A
N/A
RX3i +24Vdc Relay w/o Energy Pack
0.625 A
N/A
Input Power (Max)
20 W
Input Voltage (Min)
18 Vdc
Input Voltage (Max)
30 Vdc
Memory Backup Mechanism
21
Battery
see GFK-2741
Battery
see GFK-2741
Battery
see GFK-2741
Energy Pack:
IC695ACC400
Energy Pack:
IC695ACC400
Energy Pack:
IC695ACC402
Energy Pack:
IC695ACC403
Display
LEDs
LEDs
LEDs
LEDs
LEDs
LEDs
LEDs & OLED
17
For CRU-type CPUs, see Redundancy section at bottom of this table.
18
Where different, CPE302 value is shown in parentheses (). Also note that first Firmware Version of CPE302 was FW 9.40.
19
LT versions of the hardware are rated from -40°C to 60°C.
20
The maximum operating temperature varies according to installation altitude: 70C at 0m to 2000m, 65C at 2000m to 3000m, and 60C at 3000m to 4000m.
21
See Battery Compatibility and Memory Retention (Time in Days at 20°C) in GFK-2741

Table of Contents

Other manuals for GE PACSystems RX7i

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE PACSystems RX7i and is the answer not in the manual?

GE PACSystems RX7i Specifications

General IconGeneral
BrandGE
ModelPACSystems RX7i
CategoryController
LanguageEnglish

Related product manuals