Chapter 3. CPU Configuration
GFK-2222AD April 2018 119
Scan Parameters
Window Timer
(ms)
(Available only when Sweep Mode is set to Constant Window.) The maximum combined
execution time per scan for the Controller Communications Window, Backplane
Communications Window, and Background Communications Window. This value cannot
be greater than the value for the watchdog timer.
Valid range: 3 through 255, in increments of 1.
Default: 10.
Number of Last
Scans
(Available only for CPUs with firmware version 1.5 and greater.)
The number of scans to execute after the PACSystems CPU receives an indication that a
transition from RUN Mode to STOP Mode should occur. (Used for STOP and STOP-Fault, but
not STOP-Halt.)
Choices: 0, 1, 2, 3, 4, 5.
Default:
0 when creating a new PACSystems target.
0 when converting a Series 90-70 target to a PACSystems target.
1 when converting a Series 90-30 target to a PACSystems target.