Chapter 2. CPU Features & Specifications 
GFK-2222AD  April 2018  25 
  Downloading a Project from the RDSD to the CPU 
To download a project to the RX3i, the RDSD must contain a valid project, consisting of the hardware 
configuration, application logic, and reference memory in a compiled format (originating from another 
RX3i controller). The project files, consisting of the entire contents of the PACS_Folder directory and all 
of its subdirectories, loaded on the RDSD must not be modified. If they are modified, the files transferred 
to the CPU will be invalid. 
By default, all project components are stored to the CPU and are written to flash. You can change this 
operation by placing an options.txt file on the RDSD as described below. 
1.  Ensure that the RX3i is in STOP Mode 
2.  If PROFICY Machine Edition is online with the RX3i, either go Offline or select Monitor mode. 
3.  Connect the RDSD to the USB connector on the CPU that will be receiving the files. The RDSD LED 
turns solid green.  
4.  For  CPE302/CPE305/CPE310,  move  the  RDSD  direction  switch  to  the  right  (DOWNLOAD),  then 
momentarily depress the START pushbutton. For CPE330, depress the RDSD DNLD pushbutton. 
5.  Do not remove the RDSD from the CPU during the transfer.  
â–ª  If the target name in the RDSD is different from the target name in the RX3i, the RDSD LED will 
blink red. If this is expected or acceptable, momentarily depress the START pushbutton again. 
▪  The RDSD LED blinks green during the transfer. This can take from 10 – 150 seconds, depending 
upon the size of the project data. 
â–ª  The  RDSD  LED  should  turn  solid  green,  indicating  that  the  transfer  completed  successfully. 
Unless the RUN/STOP Switch has been disabled in the hardware configuration just stored, it can 
be used to place the RX3i into RUN Mode after the transfer. 
â–ª  If the RDSD LED turns solid red, the transfer has failed.  
-  The target memory area(s) in the CPU  are cleared. For example, if only the Logic is being 
download from the RDSD and the store fails (e.g. stick pulled, problem with transfer or data), 
Logic memory is cleared following the failed RDSD download. If other memory areas were 
also queued up for transfer, those memory areas are also cleared as a result of the failure. 
-  There will be a copy of the fault tables as they existed at the end of the attempted transfer 
on the RDSD. Insert the RDSD into a PC which has the PACS Analyzer software and select 
the plcfaultafter.dat file on the RDSD for fault table analysis by the Analyzer. 
-  If  the  RDSD  LED  turns  solid  red,  indicating  an  error,  another  RDSD  operation  cannot  be 
initiated until the device is disconnected then reconnected. 
Caution 
If the RDSD is removed during data transfer to the CPU, the 
RX3i controller will generate a fatal fault (sequence store fault) 
and SYS FLT LED will turn red. You will need to clear the fault 
tables through a programmer connection or by power cycling 
the CPU with the Energy Pack disconnected before attempting 
to download again. Each type of data being downloaded (logic, 
config, and/or data) is cleared within the target CPU.