Chapter 2. CPU Features & Specifications
GFK-2222AD April 2018 65
Ethernet Indicators CPE330 (embedded in RJ45 connectors)
On
Blinking
Off
LED
LED State
Operating State
LINK (upper)
On Green
The corresponding link is physically connected.
Blinking Green
Traffic is detected at the corresponding port.
Off
No connection detected at the corresponding port.
1Gbps (lower)
On Amber (LAN1)
or
Corresponding network data speed is 1 Gbps.
On Green (LAN2)
Off
Corresponding network data speed is 100 Mbps or 10 Mbps.
Error Checking and Correction
RX3i Redundancy CPUs provide error checking and correction (ECC), which results in slightly slower
system performance, primarily during power-up, because it uses an extra 8 bits that must be initialized.
For details on ECC, refer to the PACSystems Hot Standby CPU Redundancy User Manual, GFK-2308.
Note: Multiple Recoverable Memory Error faults may be generated when a single-bit ECC error is
detected. When a single-bit ECC error is detected, the value presented to the
microprocessor is corrected. However, the value stored in RAM is not corrected until the next
time the microprocessor writes to that RAM location.

Table of Contents

Other manuals for GE PACSystems RX7i

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE PACSystems RX7i and is the answer not in the manual?

GE PACSystems RX7i Specifications

General IconGeneral
BrandGE
ModelPACSystems RX7i
CategoryController
LanguageEnglish

Related product manuals