GE Power Management PQM Power Quality Meter 8-11
8 DNP COMMUNICATIONS 8.1 DNP 3.0 PROTOCOL
8
63 0480 Voltage Vbc THD 0.1 x % 5.0% F1 3
64 0481 Voltage Vca THD 0.1 x % 5.0% F1 3
65 04B4 Average Current THD 0.1 x % 5.0% F1 3
66 04B5 Average Voltage THD 0.1 x % 5.0% F1 3
67 0246 Phase A Current - Minimum 1000ths of nominal A 1 unit F1 3
68 0247 Phase B Current - Minimum 1000ths of nominal A 1 unit F1 3
69 0248 Phase C Current - Minimum 1000ths of nominal A 1 unit F1 3
70 0249 Neutral Current - Minimum 1000ths of nominal A 1 unit F1 3
71 024A Current Unbalance - Minimum tenths of 1 percent 1 unit F1 3
72 024B Phase A Current - Maximum 1000ths of nominal A 1 unit F1 3
73 024C Phase B Current - Maximum 1000ths of nominal A 1 unit F1 3
74 024D Phase C Current - Maximum 1000ths of nominal A 1 unit F1 3
75 024E Neutral Current - Maximum 1000ths of nominal A 1 unit F1 3
76 024F Current Unbalance - Maximum tenths of 1 percent 1 unit F1 3
77 0291 Voltage Van - Minimum 1000ths of nominal V 1 unit F3 3
78 0293 Voltage Vbn - Minimum 1000ths of nominal V 1 unit F3 3
79 0295 Voltage Vcn - Minimum 1000ths of nominal V 1 unit F3 3
80 0297 Voltage Vab - Minimum 1000ths of nominal V 1 unit F3 3
81 0299 Voltage Vbc - Minimum 1000ths of nominal V 1 unit F3 3
82 029B Voltage Vca - Minimum 1000ths of nominal V 1 unit F3 3
83 029D Voltage Unbalance - Minimum 0.1 x % 1 unit F1 3
84 029E Voltage Van - Maximum 1000ths of nominal V 1 unit F3 3
85 02A0 Voltage Vbn - Maximum 1000ths of nominal V 1 unit F3 3
86 02A2 Voltage Vcn - Maximum 1000ths of nominal V 1 unit F3 3
87 02A4 Voltage Vab - Maximum 1000ths of nominal V 1 unit F3 3
88 02A6 Voltage Vbc - Maximum 1000ths of nominal V 1 unit F3 3
89 02A8 Voltage Vca - Maximum 1000ths of nominal V 1 unit F3 3
90 02AA Voltage Unbalance - Maximum 0.1 x % 1 unit F1 3
91 030C 3 Phase Real Power - Minimum 1000ths of nominal W 1 unit F4 3
92 030E 3 Phase Reactive Power Minimum 1000ths of nominal
kvar
1 unit F4 3
93 0310 3 Phase Apparent Power Minimum 1000ths of nominal VA 1 unit F3 3
94 0312 3 Phase Power Factor - Minimum % 1 unit F2 3
95 0313 3 Phase Real Power - Maximum 1000ths of nominal 1 unit F4 3
96 0315 3 Phase Reactive Power Maximum 1000ths of nominal 1 unit F4 3
97 0317 3 Phase Apparent Power Maximum 1000ths of nominal 1 unit F3 3
98 0319 3 Phase Power Factor - Maximum % 1 unit F2 3
99 031A Phase A Real Power - Minimum 1000ths of nominal 1 unit F4 3
Table 8–1: POINT LIST FOR ANALOG INPUT/OUTPUT CHANGE (Sheet 3 of 5)
POINT MOBUS
REG
DESCRIPTION UNIT / VALUE DEADBAND FORMAT
CODE
EVENT CLASS
ASSIGNED TO
see footnote explanations at the end of the table

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Power Quality Meter Series and is the answer not in the manual?

GE Power Quality Meter Series Specifications

General IconGeneral
BrandGE
ModelPower Quality Meter Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals