GE Power Management PQM Power Quality Meter 8-11
8 DNP COMMUNICATIONS 8.1 DNP 3.0 PROTOCOL
8
63 0480 Voltage Vbc THD 0.1 x % 5.0% F1 3
64 0481 Voltage Vca THD 0.1 x % 5.0% F1 3
65 04B4 Average Current THD 0.1 x % 5.0% F1 3
66 04B5 Average Voltage THD 0.1 x % 5.0% F1 3
67 0246 Phase A Current - Minimum 1000ths of nominal A 1 unit F1 3
68 0247 Phase B Current - Minimum 1000ths of nominal A 1 unit F1 3
69 0248 Phase C Current - Minimum 1000ths of nominal A 1 unit F1 3
70 0249 Neutral Current - Minimum 1000ths of nominal A 1 unit F1 3
71 024A Current Unbalance - Minimum tenths of 1 percent 1 unit F1 3
72 024B Phase A Current - Maximum 1000ths of nominal A 1 unit F1 3
73 024C Phase B Current - Maximum 1000ths of nominal A 1 unit F1 3
74 024D Phase C Current - Maximum 1000ths of nominal A 1 unit F1 3
75 024E Neutral Current - Maximum 1000ths of nominal A 1 unit F1 3
76 024F Current Unbalance - Maximum tenths of 1 percent 1 unit F1 3
77 0291 Voltage Van - Minimum 1000ths of nominal V 1 unit F3 3
78 0293 Voltage Vbn - Minimum 1000ths of nominal V 1 unit F3 3
79 0295 Voltage Vcn - Minimum 1000ths of nominal V 1 unit F3 3
80 0297 Voltage Vab - Minimum 1000ths of nominal V 1 unit F3 3
81 0299 Voltage Vbc - Minimum 1000ths of nominal V 1 unit F3 3
82 029B Voltage Vca - Minimum 1000ths of nominal V 1 unit F3 3
83 029D Voltage Unbalance - Minimum 0.1 x % 1 unit F1 3
84 029E Voltage Van - Maximum 1000ths of nominal V 1 unit F3 3
85 02A0 Voltage Vbn - Maximum 1000ths of nominal V 1 unit F3 3
86 02A2 Voltage Vcn - Maximum 1000ths of nominal V 1 unit F3 3
87 02A4 Voltage Vab - Maximum 1000ths of nominal V 1 unit F3 3
88 02A6 Voltage Vbc - Maximum 1000ths of nominal V 1 unit F3 3
89 02A8 Voltage Vca - Maximum 1000ths of nominal V 1 unit F3 3
90 02AA Voltage Unbalance - Maximum 0.1 x % 1 unit F1 3
91 030C 3 Phase Real Power - Minimum 1000ths of nominal W 1 unit F4 3
92 030E 3 Phase Reactive Power Minimum 1000ths of nominal
kvar
1 unit F4 3
93 0310 3 Phase Apparent Power Minimum 1000ths of nominal VA 1 unit F3 3
94 0312 3 Phase Power Factor - Minimum % 1 unit F2 3
95 0313 3 Phase Real Power - Maximum 1000ths of nominal 1 unit F4 3
96 0315 3 Phase Reactive Power Maximum 1000ths of nominal 1 unit F4 3
97 0317 3 Phase Apparent Power Maximum 1000ths of nominal 1 unit F3 3
98 0319 3 Phase Power Factor - Maximum % 1 unit F2 3
99 031A Phase A Real Power - Minimum 1000ths of nominal 1 unit F4 3
Table 8–1: POINT LIST FOR ANALOG INPUT/OUTPUT CHANGE (Sheet 3 of 5)
POINT MOBUS
REG
DESCRIPTION UNIT / VALUE DEADBAND FORMAT
CODE
EVENT CLASS
ASSIGNED TO
see footnote explanations at the end of the table