796688 (4188-657)_I1.2 / 02.02
19
Fire routing equipment
The system 800 panel can activate fire
routing equipment, such as an auto
dialer in the event of a fire condition in
the system. The panel can be
configured to output either a voltage free
signal or a 24V output to trigger the
external equipment.
Using the menu controls at the panel the
fire routing equipment operation can be:
Manually activated or de-activated
Output can be enabled or disabled
A delay of up to 10 minutes can be
set up before automatic output action
The monitoring of the output can be
enabled or disabled.
Electronic
Module
Control panel
I/P
P18
0V C NO NC
P23
P22
1
2
3
1
2
3
+24V
Activation
confirmation
input
Coil resistance
650R
(
nominal
)
0V
Auto-dialler e
q
uipment
(
Such as Di
g
icom
or Red Care
)
Activation
output to tri
gg
er
auto dialer
0 -10K resistance
confirmation
output
Factor
y
default
link settin
g
s
Electronic
Module
Control panel
I
/
P
P18
0V C NO NC
P23
P22
1
2
3
1
2
3
Activation
confirmation
input
Auto-dialler e
q
uipment
(
Such as Di
g
icom
or Red Care
)
Volta
g
e free activation
output to tri
gg
er
auto dialler
0 -10K resistance
confirmation
output