796688 (4188-657)_i2 _06/03
21
Commissioning
process
Without an
power applied to the panel:
1. Verif
the continuit
of the loop circuit wirin
,
The cable resistance should be 13ohms max. at 1Km.
DO NOT UNDERTAKE HIGH VOLTAGE TESTS WITH WIRING
CONNECTED TO THE LOOP DEVICES, SUCH AS TO THE BASE.
2. Verif
the continuit
of the sounder circuit wirin
.
With circuit connected the 10Kohms end-of-line
resistance can be measured.
Connect the mains and batter
suppl
to th e
panel and once powered up:
1. Carr
out a Displa
test accessible at access level 2
and check all the indicators are workin
.
2. Setup the s
stem clock, accessible at access level 3.
3. Carr
out temporar
disconnection and re-connection
of batter
, mains suppl
and sounder circuits
and check fault indications are
iven of disconnections.
Connect the loop circuit:
1. Check the address allocation with onl
loop end-1 connected,
note a loop open circuit fault is displa
ed.
Repeat the test with onl
loop end-2 connected and then
with both ends connected.
2. Carr
out open circuit and short circuit tests on the +ve and -ve lines
of the loop circuit, re-allocate the loop after each test.
3. Re allocate the loop, confi
ure the Hardware link to allow data
to be saved at the panel and save the loop map data to the
panel EEPROM.
Confi
uration:
1. Assi
n devices to zones
2. Label devices and zones.
3. Connect, confi
ure and test other equipment
connected to the panel.
4. On completion of chan
es to confi
uration data and with
data saved to the EEPROM, reset the hardware
link to position 2-3 to write protect the EEPROM.
Fire plan:
1. Test the fire plan.
2. Check alarm sound levels in all areas of the buildin
(s).
Handover:
1. Ensure all interested parties are informed the fire alarm
s
stem is active.
2. Fill in the lo
book and provide advise on user responsibilit
and the need to maintain the s
stem in accordance with BS5839:Part 1.