EasyManua.ls Logo

heat-timer ETV Platinum Plus - Wiring aux Inputs-Sensors or

heat-timer ETV Platinum Plus
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
|
HEAT-TIMER CORP.
059305–00 REV. E
1 To connect an Auxiliary temperature sensor:
a Run the sensor wires through a knockout located on the bottom of the ETV enclosure.
b Connect the sensor wires to terminal 22 and 23 on the ETV module.
c Connect the shield to terminal 23 on the ETV module.
2 To connect a second Auxiliary temperature sensor:
a Run the sensor wires through a knockout located on the bottom of the ETV enclosure.
b Connect the sensor wires to terminal 24 and 25 on the ETV module.
c Connect the shield to terminal 25 on the ETV module.
04 INSTALLATION INSTRUCTIONS
NOTE
No voltage can be applied to terminals 22 and 23 or terminal 24 and 25.
Auxiliary inputs can be configured as temperature sensors or as switch sensors.
When configured as a switch sensor, it must be connected to a device that provides
an open or close (short) only.
Standard brass tube sensors (Heat-Timer P/N 904220–00) can be used in a well if
the temperature sensor is only monitoring the temperature. However, the standard
brass tube sensor in a well is not recommended when using the Feed Forward
function (refer to “Return Comp.” on page 44). The use of Probe Sensor (Heat Timer
P/N 904222–00) is strongly recommended for the Feed Forward function.
NOTE
The sensor wires can be extended up to 500 feet (152.5 meters) using an 18 AWG shielded 2-conductor cable
(Heat-Timer P/N 703001–01 or equivalent #18/2 cable).
NOTE
The sensor wires can be extended up to 500 feet (152.5 meters) using an 18 AWG shielded 2-conductor cable
(Heat-Timer P/N 703001–01 or equivalent #18/2 cable).
NOTE
Do not connect the shield at the sensor end.
WIRING AUX INPUTS—SENSORS OR SWITCHES (OPTIONAL)
SHIELD
SYSTEM
SENSOR

Table of Contents

Related product manuals