LOCKOUT MENU
The Lockout menu is used to reset system lockouts.
RESET LOCKOUT
Selections: RESET Default: N/A
Available in Control Mode: HTLV or ETV + HTLV
Menu Path: Lockout
Description:
The HTLV Lockout outputs energize whenever the System Temperature
rises above the Alarm Limit for the Trigger Delay period.
To reset the lockout, the conditions causing the lockout must be corrected first. Then,
the lockout can be reset using the Reset Lockout menu. If the lockout was reset before
the conditions are corrected, the lockout output will immediately be re-activated.
----- MAINTENANCE ----
System Trim 0
o
F
Outdoor Trim 0
o
F
Soft-Off-Delay 45sec
<Output Trim>
<Configuration>
BACK ▲▼SELECT
SYSTEM
A
B
C
D
Full Modulation Sequencing Control
1
2
RUNPROGRAM
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 12VA MAX
INPUT RATINGS:
USE COPPER CONDUCTORS ONLY
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
PROVE
/DHW
SHUTDOWN
/TSTAT
/SETBACK
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
Mini-MOD
SYSTEM SENSOR TRIM
+0
o
F
[ ]
BACK ▲▼ SAVE
OUTDOOR SENSOR TRIM
+0
o
F
[ ]
BACK ▲▼ SAVE
-- SOFT-OFF DELAY --
45sec
[ ]
BACK ▲▼ SAVE
------- STAGE A -------
OUTPUT TRIM
+0.0
[ ]
BACK ▲▼ SAVE
SYSTEM SENSOR TRIM
+0
o
F
[ ]
BACK ▲▼ SAVE
OUTDOOR SENSOR TRIM
+0
o
F
[ ]
BACK ▲▼ SAVE
-- STAGE A TRIM ---
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK ▲▼ SAVE
----- MAINTENANCE ----
System Trim 0
o
F
Outdoor Trim 0
o
F
Soft-Off-Delay 45sec
<Output Trim>
<Configuration>
BACK ▲▼SELECT
SYSTEM
A
B
C
D
Full Modulation Sequencing Control
1
2
RUNPROGRAM
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 12VA MAX
INPUT RATINGS:
USE COPPER CONDUCTORS ONLY
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3
4
5
6
7
8
9
10
11
12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30
31
L
N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
CAUTION: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
PROVE
/DHW
SHUTDOWN
/TSTAT
/SETBACK
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
Mini-MOD
SYSTEM SENSOR TRIM
+0
o
F
[ ]
BACK ▲▼ SAVE
OUTDOOR SENSOR TRIM
+0
o
F
[ ]
BACK ▲▼ SAVE
-- SOFT-OFF DELAY --
45sec
[ ]
BACK ▲▼ SAVE
------- STAGE A -------
OUTPUT TRIM
+0.0
[ ]
BACK ▲▼ SAVE
SYSTEM SENSOR TRIM
+0
o
F
[ ]
BACK ▲▼ SAVE
OUTDOOR SENSOR TRIM
+0
o
F
[ ]
BACK ▲▼ SAVE
-- STAGE A TRIM ---
Output Trim +0.0
<Prev Stage>
<Next Stage>
BACK ▲▼ SAVE
06 DISPLAY AND PROGRAMMING
NOTE
A Lockout condition is only generated when Control Mode is set to HTLV or ETV + HTLV (See “Control Mode” on page 44).
Under specific conditions, the control triggers the alarm and logs the event in the Alarm Log (See “Alarm Log” on page 54).
SYS
MENU
1
2
Target = 120°F
Mod. Out = 70%
HTLV Limit = 160°F
50°F
°F
120
LOCKOUT