EasyManua.ls Logo

HEIDENHAIN iTNC 530 HSCI - Page 158

HEIDENHAIN iTNC 530 HSCI
654 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
February 2012 12 – 159
Example 2:
PLC supply voltage interrupted at PLB 6204 system module
The following message is displayed:
The control has detected that an HSCI device is missing.
In the columns Previous and Now the display stops at where there are differences.
In this example there is no communication with the PLB 6204. If you scroll up a bit in the Previous
column, you will find the line identCabinet:= "591832-02",.
This is the ID of a PLB 6204 that is missing in the Now column.
8 Press the Reject button (the configuration with the missing HSCI device should not be loaded).
--> The control resumes booting and shows this error message:
8 Call the HSCI bus diagnosis.

Table of Contents

Other manuals for HEIDENHAIN iTNC 530 HSCI

Related product manuals