February 2012 28 – 477
X31:
UEC power supply
With a power supply of 400 V, the inverter voltage U
Z
is 565 Vdc, and with a power supply of 480 V
it is 678 Vdc.
EN 61800-5-1 requires a non-detachable connection to the line power supply.
If the power supply is other than 400 V, an autotransformer is required. It must comply at least
with the connection specifications of the UEC 11x.
Connecting terminals UEC 111, UEC 112
Operation on 400 V~
L1 400 V~ ± 10 %
50 Hz to 60 Hz
L2
L3
Cable / single conductor (HT wire):
6 mm
2
(AWG 10)
Single conductor H07 V2-K:
4 mm
2
(AWG 10)
Line fuse:
25 A (gR) semiconductor fuse, Siemens Sitor type
Grounding terminal:
≥ 10 mm
2
(AWG 6)
Tightening torque for connecting terminals:
0.7 Nm (6.5 to 7 psi)
Operation on 480 V~
L1 480 V~ ± 10 %
50 Hz to 60 Hz
L2
L3
Cable / single conductor (HT wire):
6 mm
2
(AWG 10)
Single conductor H07 V2-K:
4 mm
2
(AWG 10)
Line fuse:
25 A (gR) semiconductor fuse, Siemens Sitor type
Grounding terminal:
≥ 10 mm
2
(AWG 6)
Tightening torque for connecting terminals:
0.7 Nm (6.5 to 7 psi)