OperationalNon-OperationalSpecication
-300m to 3048m / -984 ft. to 10,000 ft.-300m to 12,000m / -984 ft. to 39,370 ftAltitude
Table 2: Electrical Specifications
ValueSpecication
~1250WMax Power Consumption
~1000WTypical Power Consumption
Note: Max and Typical Power Consumption
values represent the output power to the
system. Input power will vary depending on
the PSU efficiency and load sharing between
PSUs
200 - 240 VACInput Voltage
C14PSU Connector Type
80 PLUS PlatinumPSU Efciency
AC line inrush current shall not exceed 40A peak for up
to one-quarter of the AC cycle, after which, the input
Inrush Current Maximum (per PSU)
current should be no more than the specied maximum
input current.
Caution: The Ultrastar Data60 can only be plugged into highline. If the unit is plugged into lowline, the
PSU will report a "Critical" state when status pages are queried using SES. In this case, the enclosure
will power up, but the drives will not. The enclosure will remain in low-power mode.
Table 3: Mechanical Specifications
OperationalNon-OperationalSpecication
5G, 0 - peak, 11ms half sine; 3
positive and 3 negative pulses in each
10G, 0 - peak,11ms half sine; 3
positive and 3 negative pulses in each
axis Shock
Shock
axis- minimum 6 seconds between
shocks to allow for write/read
recovery
0.10G,0 - peak swept sine; 5 -500Hz;
1 complete sweep @ 1/2octave per
minute
0.75G, 0 - peak swept sine; 5 -500Hz;
1 complete sweep @ 1/2 octave per
minute
Vibration
79.4 kg. / 175 lbs.Weight
447mm x 890mm x 175mm / 17.67in. x 35.04in. x 6.89in.Dimensions
712 mm / 28.03in.Length without CMA
13
1 Overview
User Guide 1.4 Ultrastar Data60 Specification Summary