10.3 COMMON WIRING
! CAUTION
Alltheeldwiringandelectricalcomponentsmustcomplywithlocalcodes.
10.3.1  Electrical wiring between indoor unit and outdoor unit
•  Connect the electrical wires between the indoor unit and the 
outdoor unit, as shown below.
•  Follow local codes and regulations when performing 
electrical wiring.
•  If the refrigerant piping and the control wiring are connected 
to the units in the same refrigerant cycle.
•  Use twist pair wire (more than 0.75 mm²) for operation wiring 
between outdoor unit and indoor unit, and operation wiring 
between indoor unit and indoor unit.
•  Use 2-core wire for the operating line (Do not use wire with 
more than 3 cores).
•  Use shielded wires for intermediate wiring to protect the 
units from noise obstacle at length of less than 300 m and 
size complied with local code.
•  Open a hole near the connection hole of power source 
wiring when multiple outdoor units are connected from one 
power source line.
•  The recommended breaker sizes are detailed in the Wire 
size section.
•  In the case that a conduit tube for eld-wiring is not used, x 
rubber bushes with adhesive on the panel.
•  All the eld wiring and equipment must comply with local and 
international codes.
•  H-LINK twist pair shielded cable must be grounded in the 
outdoor unit side.
! CAUTION
Payattentiontotheconnectionoftheoperatingline.Incorrectconnection
maycausethefailureofPCB.
Power source from the outdoor IVX unit to the indoor unit 
(example)
Independent power source of outdoor IVX unit and indoor unit 
(example)
3
3
3
L1   L2   L3    NL1   L2   L3    N
L1   L2   L3    N
Nº 0 System 
Outdoor unit
Nº 0 System 
Outdoor unit
Operating Line 
(Shielded Pair Cable)
DC5V (Non-Pole Transmission,
 
H-LINK System)
Remote Control Switch 
(Twisted Shielded Pair Cable)
Operating Line 
(Twisted Shielded 
Pair Cable)
DC5V (Non-Pole 
Transmission, H-LINK 
System)
Indoor Unit Indoor Unit
Terminal board
Circuit Breaker
Earthleakage Breaker
Field Wiring
Field supplied
Optional Accessory
Remote Control Switch 
(Twisted Shielded Pair Cable)
Indoor Unit
Indoor Unit
Wiring example
Basic combinations (in the case of twin combination)
12
ON
DSW6
12
ON
DSW6
12
ON
DSW6
Operating line
Operating line
Operating line
Remote control line
Remote control line
Remote control line
Individual control 
Running ON/OFF individually 
Thermo.ON/OFF individually
Individual control 
Running ON/OFF simultaneously 
Thermo.ON/OFF individually
Simultaneous control 
Running ON/OFF simultaneously 
Thermo.ON/OFF simultaneously
ELECTRIC WIRING