10.3.2 Wire size
Connection wiring
Recommended minimum sizes for eld provided wires:
Model Power supply
Power source
cable size
Transmitting
cable size
EN60 335-1 EN60 335-1
All Indoor Units
1~ 230V 50Hz
0.75 mm²
0.75 mm²RAS-(4-6)HVNC1E 6.0 mm
2
RAS-(4-6)HNC1E 3N~ 400V 50Hz 4 mm
2
? NOTE
• Followlocalcodesandregulationswhenselectingeldwires,Circuit
breakersandEarthLeakagebreakers
• Usethewireswhicharenotlighterthantheordinarypolychloroprene
sheathedexiblecord(codedesignationH05RN-F)
Main switch protection
Select the main switches in according to the next table:
Model Power supply
Max.
current
(A)
CB
(A)
ELB
(nº poles/A/mA)
All Indoor
Units
1~ 230V 50Hz 5.0 6 2/40/30
ELB: Earth switch; CB: Circuit braker
Outdoor unit MC (A) CB (A) ELB
RAS-4HVNC1E 28.5 32
2/40/30RAS-5HVNC1E 28.5 32
RAS-6HVNC1E 28.5 32
RAS-4HNC1E 15.5 20
4/40/30RAS-5HNC1E 15.5 20
RAS-6HNC1E 15.5 20
11 COMMMISSIONING
When installation is completed, perform test run according to the following procedure, and hand over the system to the customer.
Perform test run regarding indoor units one by one in order, and conrm that the electrical wiring and the refrigerant piping are
correctly connected.
Test run should be performed according to the “11.1TestRunprocedurebyRemoteControlSwitch(PC-ARTexample)” on next
page.
! CAUTION
Donotoperatethesystemuntilallthecheckpointshavebeencleared:
• Checkto ensurethat the electrical resistance ismore than1 MΩ,
bymeasuringtheresistancebetweengroundandtheterminalofthe
electricalparts.Ifnot,donotoperatethesystemuntiltheelectrical
leakage is found and repaired. Do not impress the voltage on the
terminalsfortransmission1and2.
• Check to ensure that the stop valves of the outdoor unit are fully
opened,andthenstartthesystem.
• Checktoensurethattheswitchonthemainpowersourcehasbeen
ONformorethan12hours,to warm the compressor oil bythe oil
heater
Payattentiontothefollowingitemswhilethesystemisrunning:
• Do not touch any of the parts by hand at the discharge gas side,
sincethecompressorchamberandthepipesatthedischargeside
areheatedhigherthan90°C.
• DONOTPUSHTHEBUTTONOFTHEMAGNETICSWITCH(ES),it
willcauseaseriousaccident.
• Donottouchanyelectricalcomponentsformorethanthreeminutes
afterturningOFFthemainswitch
• Conrmthatthegaslinestopvalveandtheliquidlinestopvalveare
fullyopen.
• Conrmthattheleakageoftherefrigerantdoesnotexist.Theare
nutsaresometimesloosenedbyvibrationduringtransportation.
• Checkthattherefrigerantpipingandtheelectricalwiringconformto
thesamesystem.
• Conrmthatthedipswitchsettingontheprintedcircuitboardofthe
indoorunitsandtheoutdoorunitsarecorrect.
• Checkwhetherornottheelectricalwiringoftheindoorunitsandthe
outdoor units are connected as shown in the chapter “10 Electric
wiring”.
! CAUTION
Conrmthateld-suppliedelectricalcomponents(mainswitchfuse,fuse-
freebreaker,earthleakagebreakers,wires,conduitconnectorsandwire
terminals)have beenproperlyselectedaccordingtothe electricaldata
givenintheTechnicalCatalogoftheunitandensurethatthecomponents
complywithnationalandlocalcodes.
? NOTE
• Fortwin,tripleandquadchecktheindoorunitoutletairtemperature
attestrun.Ifthetemperaturedifferenceislarge(aprox.10deg.or
more (cooling) 20 deg. or more (heating) recheck the refrigerant
piping,Installationmayhavesomeproblem.
• Inthecaseofanualcoolingoptional function, cut JP1 outand set
theDSW6-1toOFF.(Individualcontrolisnotavailablewhenanual
coolingisselected).
COMMMISSIONING