Extinguishing Control Computer 8010 – 19-Inch
FB 798955.GB0 / 09.07 17
2.8 Resetting the panel
The Panel can be reset via the function key of the control panel. For operation, the keypad must be enabled via
the key-switch. To restart the system press the appropriate button. The internal panel status and all visual
displays will be resetted.
In operation
Unlocked
For operation, it is necessary to enable the keypad via the key-switch.
A restart of the system does not take affect on disconnected detector zones or detector zones in
the test mode. This zone will not be switched on or resetted by a restart.
Panel reset
In operation
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Emergency release
Extinguishing system
activated
Extinguishing system
enabled
Fig. 15: Operating example – panel reset
2.9 Lamp test
The lamp test can be carried out via the keypad. All visual displays of the control panel lights up and the control
panel buzzer is activated until the key is released.
In operation
Unlocked
For operation, it is necessary to enable the keypad via the key-switch.
Lamp test
12345678
910111213
Fan trouble
Common trouble
Emergency
operation
Power trouble
Battery trouble
Ground fault
Trouble 1
Blocking
Detector zone
Fire/Switch off/Trouble
In operation
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Emergency release
Extinguishing system
activated
Extinguishing system
enabled
Fig. 16: Indication and Operation – Lamp test