Extinguishing Control Computer 8010 – 19-Inch
72 FB 798955.GB0 / 09.07
11 Specification
Main voltage : 230 V AC
Rated frequency : 50 Hz
Rated current : 0,7 A
Supply voltage
for external devices : 24 V DC
Battery capacity : 2 x 12 V / 12 Ah
Battery charging voltage : 13.65 V DC @ 25 °C
Ambient conditions : class 3k5 in accordance to DIN EN 60721-3-3
Ambient temperature : -5 °C to +45 °C
Storage temperature : -10 °C to +50 °C
Protection type :
I in accordance to DIN EN 60950-1
Protection rating : IP 30
Housing : Sheet steel
Colour : Light grey, similar RAL 7035 / blue, similar RAL 5003
Weight : approx. 10,1 kg (without rechargeable battery)
Dimensions (W x H x D): : 483 x 132 x 403 (mm), without handle bars
VdS approval : G 200090 (series 2), G 205064 (series 3)
CE certificate : 0786 – CPD - 20223
Alarm zone inputs 1 to 8 : esserbus
®
zone:
Monitored detector zone for connecting automatic fire detectors and
series 9200 technical alarm modules, as well as esserbus
®
transponders.
Do not connect an End-of-line resistor
Standard zone:
To connect external dry contacts
End-of-line resistor (4,7k
Ω normal / 1kΩ alarm)
Technical zones : Monitored detector zone to connect series 9000 manual call points and/or
dry contacts
End-of-line resistor (10k
Ω normal / 1kΩ alarm)
Relay contacts
Relays 1 to 8 : Changeover contacts, max. 30 V DC / 2 A
Operating mode dry contact or positive-switching / monitoring can be
selected via jumpers (factory setting = monitored)
Relays 9 to 11 : Changeover contacts, max. 30 V DC / 2 A
Programmable, relays 10 and 11 with selectable function
>Emergency Operation Trouble< and >Emergency Operation Fire<
Relays 12 and 13 : Dry contact (NO), max. 230 V AC / 2 A
suitable to switch AC Mains voltage