Extinguishing Control Computer 8010 – 19-Inch
FB 798955.GB0 / 09.07 7
2.1.2 Status display of the outputs
The status of the corresponding zone or of the output is alternatively indicated with the 13 LED. The status of
the 13 zones is shown in normal operation. The output indication is activated by pressing the >Switchover< key.
The green LED >Output< of the status display lits to confirm the activated output indication.
Switchover
With the key >Switchover<
, it is possible to switch between indicating the zones or outputs
(Toggle operation).
Status display of the outputs is
switched on
123456 8
9 10111213
7
Detector zone
Fire/Switch off/Trouble
In operation
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Emergency release
Extinguishing system
activated
Extinguishing system
enabled
Fig. 3: Status display of the outputs (Example with Output No. 7)
Outputs no.1 to no.13 (yellow LED)
Off Normal operation, the output is in the resting state
Flashes Output failure
On Output deactivated
Twinkle Input check -the output number was entered via the control panel keypad
Disconnected or zones in trouble will not signal an alarm in case of an event!