Galaxy Dimension Installer Manual
6-53
01 = Bell Time
The duration of the Bells output activation is programmable within the range 0–30 minutes; the default is 15.
Assigning a value of 00 minutes sets the Bell Time to infinity.
This parameter can be assigned a different value for each group.
The Entry/Exit Horn is subject to the Bell Time parameter in both the set and unset conditions.
02 = Bell Delay
The delayed activation of the bell is programmable within the range 0–20 minutes; the default is 0. The Bell
Delay is overridden by a comms failure (either a Comms Fail on the Communication Module or by the
activation of a Line Fail zone used to monitor a digicom); an alarm condition in either of these conditions
results in instant bells activation.
This parameter can be assigned a different value for each group.
03 = Abort Time
The abort function delays the activation of a full intruder alarm condition following an entry alarm. This param-
eter has 2 sub-options:
1 = Abort Time
The abort time is programmable within the range 0-300 seconds and can be assigned a different value for each
group. The abort time will be initiated:
whenever a zone that is not on the entry route (Final, Entry and Exit zones) is activated — a
user strays from the entry route;
a valid code is not entered before the entry time expires.
The abort operation can be modified by adding a º or # to the programmed time. The standard abort
operation is as follows:
For entry route deviation, the signalling of an intruder alarm is delayed.
If a valid code is entered before the entry time expires:
(1) The intruder is not signalled.
(2) The system does not require a system reset.
If a valid code is not entered before the entry time expires or an entry timeout condition occurs:
(1) The intruder is signalled at the end of the entry time.
(2) The Abort timer starts on expiry of the entry time.
If a valid code is entered within the programmed abort time:
(1) If an abort output/channel is allocated to the alarmed group:
a) The Abort signal is sent.
b) The intruder condition is not restored.
c) Intruder restore is not signalled.
(2) If there is no abort output allocated to the alarmed group:
a) The intruder condition is restored.
b) Intruder restore is signalled
If the programmed abort time is allowed to expire without a valid code being entered, then the system
requires a system reset. The panel cannot be set until this occurs.
NOTE: If reduced resets (51.55.3) is enabled, the alarm will be reset by the user code, if the alarm is
unconfirmed.
51 - Parameters (cont’d)

Table of Contents

Other manuals for Honeywell Galaxy Dimension series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy Dimension series and is the answer not in the manual?

Honeywell Galaxy Dimension series Specifications

General IconGeneral
ModelGalaxy Dimension series
UsersUp to 250
PartitionsUp to 8
Operating Temperature-10°C to +55°C
CompatibilityHoneywell Galaxy accessories and peripherals

Related product manuals