Galaxy Dimension Installer Manual
6-58
17 = Restart
This parameter has three options:
1 = Restart
This option re-configures the system without the need to remove and reconnect the power. The system dis-
plays a WARNING!!! ent=RESET SYSTEM, press the ent key to reconfigure the system. The keypad
display becomes blank for a few seconds, then displays the message Configuring Please Wait. When
configuration is complete the banner returns to the normal display (day mode). The Restart option configures
any modules that have been added to the system but gives an alarm if there are any tampers open or if any
modules are reported as missing.
NOTE: This parameter exits engineer mode. It is however recommended that the exit engineer mode se-
quence is used when adding or removing modules from the system.
NOTE: Outputs are momentarily reset during the restart. If the system has a communications requirement,
put it on test before using the restart.
2 = Defaults
This option chooses the panel default settings for a particular country. These are: 1 = UK, 2 = Spain,
3 = Portugal, 4 = Germany, 5 = Italy.
The system displays a WARNING!!! ent=RESET SYSTEM, press the ent key to reconfigure the system.
3 = Language
This option chooses the language shown on the keypad display. These are: 1 = English, 2 = Espanol,
3 = Portugues, 4 = Deutch, 5 = Italiano. Pressing ent changes the display immediately.
18 = Stop Set
This parameter, when set to 1 (enabled), prevents the system from set override if there is a communication or
power fail condition at the time of starting the setting procedure. If the condition is the result of an open Line
Fail or AC Fail zone, then the system can not be set until the zone is closed or omitted. The Stop Set param-
eter is set to 0 (disabled) by default.
NOTE: Battery Low will also prevent the system from setting.
19 = Part Alarm
When the Part Alarm parameter is set to 1 (enabled — default setting) the Bells and Strobe outputs activate
if an alarm condition occurs when the system is part set.
When the Part Alarm parameter is set to 0 (disabled) the Bells and Strobe outputs are disabled when the
system is part set.
NOTE: The Horn, Entry/Exit and Intruder outputs are not affected by this parameter.
This parameter can be assigned a different value for each group.
51 - Parameters (cont’d)

Table of Contents

Other manuals for Honeywell Galaxy Dimension series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy Dimension series and is the answer not in the manual?

Honeywell Galaxy Dimension series Specifications

General IconGeneral
ModelGalaxy Dimension series
UsersUp to 250
PartitionsUp to 8
Operating Temperature-10°C to +55°C
CompatibilityHoneywell Galaxy accessories and peripherals

Related product manuals