Galaxy Dimension Installer Manual
6-97
09 Set (Reflex)
The Set output is activated when the assigned groups on the system are set. This output is a Reflex output
and follows the set and unset status of the groups.
10 Engineer (Reflex)
The Engineer output is activated while the engineer mode is being accessed.
11 Spare (Latch)
The Spare output has function: it is used to designate outputs that are not being used on the system.
12 Ready (Reflex)
The Ready output is active when all zones in the system (group) are closed. This output activates in both the
unset and set conditions.
13 Security (Latch)
The Security output is activated whenever a Security zone is activated. The output is not subject the Rearm
parameter: it latches on and remains active until a valid code (type 2 or above) is entered.
14 AC Fail (Reflex)
The AC Fail output indicates the status of the a.c. (mains) power supply. The output activates when the a.c.
supply fails or an AC Fail zone is activated. The output is reset when the a.c. supply is restored or the AC
Fail zone is closed. The activation is delayed subject to the time entered in the 20=Power Delay parameter.
15 Battery Low (Reflex)
The Battery Low output activates whenever the control unit stand-by battery falls below 10.5V or a Battery
Low zone is activated. The output is restored when the voltage rises above 10.5V or the Battery Low zone
is closed.
16 Fire (Latch)
The Fire output is activated whenever a Fire zone is activated. The output is not subject to the Rearm
parameter: it latches on and remains active until a valid code (type 2 or above) is entered.
17 Horn (Latch)
The Horn output is a general alarm output and is activated by most zone types in both the local and full alarm
modes. For example, a Fire zone activation causes the Horn output to pulse on and off – on for 0.5 seconds,
off for 0.1 seconds. The Horn output is subject to the Bell Time, Bell Delay and No. Rearm parameters.
53 - Program Outputs (cont’d)

Table of Contents

Other manuals for Honeywell Galaxy Dimension series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy Dimension series and is the answer not in the manual?

Honeywell Galaxy Dimension series Specifications

General IconGeneral
ModelGalaxy Dimension series
UsersUp to 250
PartitionsUp to 8
Operating Temperature-10°C to +55°C
CompatibilityHoneywell Galaxy accessories and peripherals

Related product manuals