Galaxy Dimension Installer Manual
6-191
69 - Access Control (cont’d)
69.3.2 = Card Format
This option selects what type of card is used with the DCM reader. There are five options:
0 = 26 bit
1 = Crp 1K 35 bit
2 = 37 bit no FC
3 = Northern 34 bit
4 = Custom.
1 = Format Name
This option is only available when 4 = Custom is selected as the format. It gives a name to the custom format.
The maximum number of characters in the name is 12.
2 = Card Length
The bit size of the card can be 26, 27, 32, 34, 35, 37 or 40.
3 = Start Point
If the card structure is unknown then it can be decided where the card number starts from. This is a numeric
value that must be less than the maximum length of the card.
4 = User Field
This is where the facility code is specified. Two options can be selected:
1 = Field Position
This is the start bit for the facility code. It can be from 1 to the card number start point.
2 = Field Length
This is the length of the facility code. The maximum field length is from the field position to the start of the
card number.