Revision 12 ST 700 SmartLine Pressure Transmitters User’s Manual Page 161
Table 34 – ST 700 Basic Transmitter: Standard Display Menu
English Language
Choose appropriate
engineering units from list for
calibration and writing
LRV/URV.
This selection determines the
units of the values shown on
the following menu items:
• Enter LRV
• Enter URV
• Set LRV
• Set URV
• Zero Correct
• LRV Correct
• URV Correct
• Cal Low Point
• Cal High Point
• Cal Low Correct
• Cal High Correct
• Barometric Correct
For calibration, this parameter
allows the user to match the
value displayed on the menus
to the units supported by the
user’s calibration equipment.
The limits are:
2X the Lower Range Limit
(LRL) of the Meter body and
2X the Upper Range Limit
(URL) of the Meter body.
The LRV/URV value will be
available in Pressure Units
(Simple Display pressure unit)