Page 162 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 13
DAC Zero Trim
[5ZEROTR]
Note: Loop must
be removed
from Automatic
Control
This selection allows the loop
zero output 4mA value to be
trimmed.
Note: You must connect a
current meter to the transmitter
to monitor the loop output.
Press to
enter menu
selection.
Menu to
select
number.
to enter
and shift to
the next digit
to the right.
DAC Span Trim
[6SPANTR]
Note: Loop must
be removed
from Automatic
Control
This selection allows the loop
span output 20mA value to be
trimmed.
Note: You must connect a
current meter to the transmitter
to monitor the loop output.
Loop Test
[7 LPTEST]
Note: Loop must
be removed
from Automatic
Control
This selection allows the user
to force the DAC output to any
value between 3.8 and 20.8
mA.
Note: This selection will put the
DAC into Fixed Output Mode,
as indicated by the flashing
output value. Navigation away
from this menu item will return
the loop to Normal (Automatic)
Mode.
Press to
enter menu
selection
to select
number.
to enter
and shift to
the next digit
to the right
Executing this selection
performing for Zero operation.
Note: The PV value shown in
bottom line will be available in
Pressure Units (Simple Display
pressure unit)
Press to
enter menu
selection.
Press to
initiate
action.
Executing this selection for
Span operation
Note: The PV value shown in
bottom line will be available in
Pressure Units (Simple Display
pressure unit)
Adjust the LCD contrast level.
Range from » (1) to
»»»»»»»»» (7)
Default: »»»»»»» (7)
Press to
enter Menu
selection.
Menu to
select level.
to Enter