Revision 12 ST 700 SmartLine Pressure Transmitters User’s Manual Page 183
When “User Configuration”
is selected for Low Flow
Cutoff Mode, enter the
desired breakpoint value.
Press to
enter menu
selection
to select
number.
to enter
and shift to
the next digit
to the right
SP Zero Correct
[24SPZRO]
Corrects the static pressure to
a zero value psi for DP
transmitters only
Performs the correction of
measured static pressure
value to a value of zero psi.
Executing this selection
corrects Static Pressure
Zero based on the input
static pressure.
The live value of the static
pressure input is shown on
this display so the user can
easily see the result of the
correction.
Press to
enter menu
selection
Press to
initiate action
SP Reset Correct
[25SPRST]
Executing this selection
resets Static Pressure Zero
to the factory value of 0.
Press to
enter menu
selection
Press to
initiate action
Barometric Standard
[26BARSTD]
Enter an atmospheric
pressure value
corresponding to a
barometric standard.
If the difference between the
measured atmospheric
pressure and the user-
entered barometric standard
pressure is > 1 psi
(27.680672 inH2O [4°C]) the
calibration will not be
performed.
Range: 330-490 inH2O [4°C]
Default: 406.782 inH2O
[4°C]
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right
Barometric Correct
[27BARCOR]
One point field offset
Calibration Method for AP
transmitters only
Adjusts the pressure
measured by the AP
transmitter with the user
entered barometric
standard.
Press to
enter menu
selection
Press to
initiate action