Revision 12 ST 700 SmartLine Pressure Transmitters User’s Manual Page 195
Screen4 Flow
Scaling Low
[66FSCLLO]
########
Value of the flow custom
engineering unit
corresponding to the LRV of
the transmitter
The limits are:
-999999 to 999999
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right
Screen4 Flow
Scaling High
[67FSCLHI]
########
Value of the flow custom
engineering unit
corresponding to the URV of
the transmitter
The limits are:
-999999 to 999999
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right
Screen4 Pressure
Custom Unit
[68PCUNIT]

When “Custom” selected for
Screen4 Pressure Units,
enter the custom unit name.
Character string of pressure
custom unit text for display
x = any Alphanumeric value
Press to
enter menu
selection
to select
alphanumeric
character.
to enter
and shift to
the next
character to
the right
Screen4 Pressure
Scaling Low
[69PSCLLO]
########
When “Custom” selected for
Screen4 Pressure Units,
enter the Screen4 Pressure
Scaling Low value.
Value of the pressure
custom engineering unit
corresponding to the LRV of
the transmitter
The limits are:
-999999 to 999999
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right