Page 196 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 13
Screen4 Pressure
Scaling High
[70PSCLHI]
########
When “Custom” selected for
Screen4 Pressure Units,
enter the Screen4 Pressure
Scaling High value.
Value of the pressure
custom engineering unit
corresponding to the URV of
the transmitter
The limits are:
-999999 to 999999
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right
РасМню
[EXDMNU]
Откл (DISABLE)
СтМеню (SD MENU)
Вкл (ENABLE)
->РсшМеню (EX MENU)
Select ‘Enable’ to enter ‘EX
MENU’ and ‘Disable‘to enter
into ‘SD MENU’
Press to
enter menu
selection
Menu to
select from
list
to enter
Выход
[EXIT]
Exit
Exit from Menu
Exit from
Menu list
to enter
Field Calibration for Alternate Ranges
Although all ST 700 transmitters are precisely calibrated at the factory, user calibration can be
performed at two points (Calibrate High Point and Calibrate Low Point) within the span range of
LRV to URV, but is typically unnecessary. It is critical that the pressure standard used for calibration
at these two points should be certified to at least twice the pressure transmitter’s accuracy. This is to
prevent misleading results that can occur when pressure standards are used that are considered
accurate, but in reality are worse than the accuracy of factory-calibrated transmitters.