Revision 13 ST 700 SmartLine Pressure Transmitters User’s Manual Page 53
Pressure Units
[ 1UNITS]
atm
bar
ftH2O68F
gf/cm2
inH2O39F
inH2O60F
inH2O68F
inHg0C
kgf/cm2
kPa
mbar
mmH2O4C
mmH2O68F
mmHg0C
MPa
Pa
psi
Torr
mH2O4C
cmH2O4C
Choose appropriate engineering
units from list for calibration and
writing LRV/URV
This selection determines the
units of the values shown on the
following menu items:
Enter LRV
Enter URV
Set LRV
Set URV
Zero Correct
LRV Correct
URV Correct
Cal Low Point
Cal High Point
Cal Low Correct
Cal High Correct
Barometric Correct
For calibration, this parameter
allows the user to match the
value displayed on the menus to
the units supported by the user’s
calibration equipment.
Press to
enter menu
selection
Menu to
select from
list
to enter
Enter LRV
[ 2ENTLRV]
Enter URV
[ 3ENTURV]
###. ##
###. ##
The limits are:
2X the Lower Range Limit (LRL) of
the Meter body and 2X the Upper
Range Limit (URL) of the Meter
body.
The LRV/URV value will be
available in Pressure Units
(Simple Display pressure unit)
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right
SET Zero
[4SETZRO]
Zero Trim
perform an input calibration
correction by applying process
input at zero.
Press to
enter menu
selection
Press to
initiate action