Page 56 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 13
Filter Selection
[18FLTSEL]
STDSOR
FASTSOR
Configure the desired
performance for the Output
Speed of Response Filter. Select
from: Standard SOR: excellent
speed of response to input
changes with optimal noise
performance Fast SOR: fastest
speed of response to input
changes.
Press to
enter menu
selection
Menu to
select from
list
to enter
NAMUR
[19NAMUR]
DISABLE
ENABLE
select to enable or disable the
Namur option for effect on output
signal.
Press to
enter menu
selection
Menu to
select from
list
to enter
Language Selection
[20LNGSEL]
ENGLISH
RUSSIAN
Standard display language
selection:
Select English or Russian option
to show display in selected
language.
Press to
enter menu
selection
Menu to
select from
list
to enter
Transfer Function
[21TXFRFN]
LINEAR
SQRT
Pressure Transfer function:
Select the pressure transfer
function for calculated output:
Linear: (output scaled linearly per
configured range) Square Root:
(output scaled as square root
conversion per configured range -
for flow measurements).
Press to
enter menu
selection
Menu to
select from
list
to enter
Low Flow Cut Off
Mode
[22CUTFMD]
ZROFLOW
SBRKPT
DAULSLP
Low Flow Cutoff Mode:
For Square Root (Transfer
function) configurations only,
choose the operating mode to
determine the low flow cutoff
breakpoint: Dual slope:
(breakpoint determined by dual
slope calculation) User
configuration: (breakpoint defined
by user).
Zero Flow: Sets analog output to
4mA when square root / flow is
below user defined flow cutoff
value.
Note: Sets loop output to low
saturation when the differential
pressure is below 10%Flow.
Press to
enter menu
selection
Menu to
select from
list
to enter