Revision 13 ST 700 SmartLine Pressure Transmitters User’s Manual Page 55
LRV Corrects
[11LRVCOR]
Calibration Methods
Perform an input calibration
correction by applying process
input at the configured LRV level.
Press to
enter menu
selection
Press to
initiate action
URV Corrects
[12URVCOR]
Calibration Methods
Perform an input calibration
correction by applying process
input at the configured URV level.
Press to
enter menu
selection
Press to
initiate action
Reset Corrects
[13RSTCOR]
Calibration Methods
Executing this selection resets
the Zero, LRV, URV, Cal Low,
Cal High and Barometric
Standard Corrects back to factory
values.
Press to
enter menu
selection
Press to
initiate action
Tag Id
[14TAGID]

Character string of device tag text
for display
x = any Alphanumeric value.
Press to
enter menu
selection
to select
alphanumeric
character.
to enter
and shift to
the next
character to
the right
Device Firmware
[15DEVFW]

Menu item shows the current
Firmware version of the device. x
= any numeric value.
Menu to
select from
list
to enter
Sensor Firmware
[16SENFW]

Menu item shows the current
Firmware version of the sensor. x
= any numeric value.
Menu to
select from
list
to enter
PV Damping
[17PVDAMP]
##.#
Enter a value for damping of the
device output. Entries may be
any value from 0.00 to 32.00
seconds.
Press to
enter menu
selection
to select
number.
to enter
and shift to
the next digit
to the right