Chapter 7 Troubleshooting and Maintenance
54 MONT20 User Manual V1.6
Fault Reason Countermeasure
E0007
MONT20 overloaded
Load of door motor is too large
Door motor is resisted by obstacle
Adjust the mechanical device
Check mechanical device for anything
resisting it
E0008
Permanent magnet
Syn. motor first
current detection is
too small
When the first power-on mode of
the permanent magnet Syn. motor
is selected as the pulse method
(F06.25 hundred = 1), the detected
current is too small
Check the motor wiring and wire
properly
Check if the door controller output is
normal
E0009
Motor overload fault
Excessive load on door motor
A foreign object blocked the door
motor
Adjust mechanism
Check mechanical devices to remove
foreign object
Improper parameter setting of door
controller
E0010
Abnormal opening
fault
The motor was blocked for 10
consecutive times
Adjust mechanism
Check mechanical device to remove
foreign object
Improper parameter setting of door
controller
E0011
Motor overheating
fault
External motor overheating signal is
detected
Motor overheating switch action
E0012
Abnormal closing fault
After the motor is powered on, the
CD complete signal is never
detected, and the number of CD
blocked exceeds 20 times
Adjust mechanism
Check mechanical devices to remove
foreign object
Improper setting of door controller
parameters
E0014
Read/write fault of
controller EEPROM
Memory circuit fault of controller
EEPROM
Contact the supplier for repairing
E0015
Speed deviation is too
large
In the range of F10.16, the actual
speed is greater than the given
speed and exceeds the set value of
F10.15
Check if the F10.15 - F10.16 are set
properly
Check encoder wiring
Redo self-tuning
E0016
Overspeed fault
The actual speed detected in the
range of F10.18 is greater than the
motor rated frequency F10.17
Check if the F10.17 - F10.18 are set
properly
Check encoder wiring
Redo self-tuning