Figure 4-86 Installing the re cylinder steel straps
(1) Fire cylinder steel straps
Step 8 Connect cables of the electromagnetic valve to the interconnection terminal.
Figure 4-87 Connecting cables to the electromagnetic valve
Step 9 Connect the cables to the pressure announciator.
Step 10 Reinstall the adapter and high-pressure hose.
Step 11 Connect the cables between the electromagnetic valve and the
re alarm control
panel.
Step 12 After installing the
re cylinder, remove the safety pin on the re cylinder.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 4 Parts Replacement
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 139