6 Power-On Commissioning
Copyright © Huawei Technologies Co., Ltd.
268
Table 6-19 Setting teamwork control parameters for two smart cooling products
Parameter
Smart Cooling Product No.
1
2
Teamwork function
Enable
Enable
Teamwork group no.
1
1
Teamwork unit address
1
2
Total number of units
2
N/A
Number of running units
1 (1 standby smart cooling product)
N/A
Rotation
Enable
N/A
Rotation period
The parameter can be set by the day ranging
from one day to 30 days as required.
N/A
Rotation time
The parameter can be set by the hour
ranging from midnight to 23:00 as required.
N/A
Requirement control
Competitive running avoidance
N/A
Table 6-20 Setting teamwork control parameters for three smart cooling products
Parameter
Smart Cooling Product No.
1
2
3
Teamwork function
Enable
Enable
Enable
Teamwork group no.
1
1
1
Teamwork unit
address
1
2
3
Total number of units
3
N/A
N/A
Number of running
units
2 (1 standby smart cooling product)
N/A
N/A
Rotation
Enable
N/A
N/A
Rotation period
The parameter can be set by the day
ranging from one day to 30 days as
required.
N/A
N/A
Rotation time
The parameter can be set by the
hour ranging from midnight to
23:00 as required.
N/A
N/A
Requirement control
Competitive running avoidance
N/A
N/A

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals