FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
3 Hardware Installation
Copyright © Huawei Technologies Co., Ltd.
58
The height deviation refers to the distance from the stop valves of the indoor unit to the
stop valves of the outdoor unit.
is a sign of a tilt, and it indicates that the scale of the pipe tilting is 1:200. The pipe
tilting direction should be consistent with the hypotenuse of the right triangle.
Figure 3-31 Layout of upward piping
(1) Oil trap
(2) Tilted gas pipe
(3) Indoor unit
(4) Tilted liquid pipe