6. Description of Parameters
- 126 -
6
Related parameters are described as follows:
Function Code Parameter Name Setting Range Default
F1-00
Motor type selection 0: Common asynchronous motor
1: Variable frequency asynchronous motor
1
F1-01
Rated motor power 0.1 to 1000.0 kW Model
dependent
F1-02
Rated motor voltage 1 to 2000 V Model
dependent
F1-03
Rated motor current 0.01 to 655.35 A (AC drive power ≤ 55 kW)
0.1 to 6553.5 A (AC drive power > 55 kW)
Model
dependent
F1-04
Rated motor
frequency
0.01 Hz to max. frequency Model
dependent
F1-05
Rated motor speed 1 to 65535 RPM Model
dependent
F1-00 to F1-05 are motor nameplate parameters. Set them correctly according to motor
nameplate to ensure accurate motor auto-tuning result. Advantages of V/F, SVC or FVC can be
obtained only after correct motor parameters are applied.
Function Code Parameter Name Setting Range Default
F1-06
Stator resistance 0.001 to 65.535 Ω (AC drive power ≤ 55 kW)
0.0001 to 6.5535 Ω (AC drive power > 55 kW)
Model
dependent
F1-07
Rotor resistance 0.001 to 65.535 Ω (AC drive power ≤ 55 kW)
0.0001 to 6.5535 Ω (AC drive power > 55 kW)
Model
dependent
F1-08
Leakage inductive
reactance
0.01 to 655.35 mH (AC drive power ≤ 55 kW)
0.001 to 65.535 mH (AC drive power > 55 kW)
Model
dependent
F1-09
Mutual inductive
reactance
0.1 to 6553.5 mH (AC drive power ≤ 55 kW)
0.01 to 655.35 mH (AC drive power > 55 kW)
Model
dependent
F1-10
No-load current 0.01 to F1-03 (AC drive power ≤ 55 kW)
0.1 to F1-03 (AC drive power > 55 kW)
Model
dependent
F1-06 to F1-10: These function parameters are asynchronous motor parameters and can be
obtained through motor auto-tuning. Only F1-06 to F1-08 can be obtained through static auto-
tuning. F1-06 to F1-10 as well as F1-30 (
A/B phase sequence of ABZ incremental encoder
) can be
obtained through dynamic auto-tuning.
If motor auto-tuning cannot be performed on site, set these parameters according to data
provided by motor manufacturer.

Table of Contents