6. Description of Parameters
- 146 -
6
6.6.11 Output Overcurrent Protection
This is to provide overcurrent protection for the AC drive.
If the drive's output current is equal to or smaller than the value set in F8-36 and the duration
exceeds the value set in F8-37, digital output terminal set for function 36 becomes on.
Figure 6-47 Output current limit
Time
Time
F8-36
ON
F8-37
Output current
Output
overcurrent
detection signal
Function Code Parameter Name Setting Range Default
F8-36
Output overcurrent threshold 0.0% (no detection)
0.1% to 300.0% (rated motor
current)
200.0%
F8-37 Output overcurrent detection
delay
0.00s to 600.00s 0.00s

Table of Contents