6. Description of Parameters
- 96 -
Step 2: Select a required curve for AI terminal.
F4-33 selects curve of AI1, AI2 and AI3 from the ve curves, respectively. Curve 1, curve
2 and curve 3 are 2-point curves, set in group F4. Curve 4 and curve 5 are 4-point curves,
set in group A6.
The drive provides two AI terminals (AI1, AI2). An extra AI terminal (AI3) is provided by
the I/O extension card.
Function Code Parameter Name Setting Range Default
F4-33
AI curve selection
Curve 1 (2 points, see
F
4
-
1
3
t
o
F
4
-
1
6
)
Curve 2 (2 points, see
F
4
-
1
8
to
F
4
-
2
1
)
Curve 3 (2 points, see
F
4
-
2
3
to
F
4
-
2
3
)
Curve 4 (4 points, see
A
6
-
0
0
to
A
6
-
0
7
)
Curve 5 (4 points, see
A
6
-
0
8
to
A
6
-
1
5
)
321
Units position: AI1 curve selection
Tens position: AI2 curve selection
Hundreds position: AI3 curve selection
F4-17
AI1 lter time 0.00s to 10.00s 0.10s
F4-22
AI2 lter time 0.00s to 10.00s 0.10s
F4-27
AI3 lter time 0.00s to 10.00s 0.10s
F4-17, F4-22 and F4-27 set AI software lter time. If analog input is liable to interference,
increase this parameter to stabilize detected analog input. But too large a setting slows
response of analog detection. Set it correctly based on actual conditions.
Step 3: Select a required AI terminal as main frequency reference setting channel.
The AC drive provides two AI terminals (AI1, AI2). An extra AI terminal (AI3) is provided by
the I/O extension card.
Here takes each AI terminal as examples to show how to use AI terminal to control main
frequency reference.
Example 1: To make voltage input at AI1 to control frequency reference and correspond 2
to 10 V to 10 to 40 Hz, the settings are shown in the following gure.
Figure 6-16 Voltage input at AI1 to control frequency reference
Note:
2 to 10 V corresponds to 20.0% to 80.0%.
100.0% corresponds to max. frequency (F0-10 = 50.00 Hz).
AI1
F4-33 (units
position) = 1
Select two-point
curve 1 for AI1
0 to 10 V
Pot.
(2 kΩ)
F4-13
F4
-14
2.00
F4-15
F4-16
10.00
F4-17 0.10
AI (V)
80.0
60.
0
40.0
20.0
0.00
2.00 4.006.008.0010.00
F4-14
0.0
F4-13 F4-15
F4-16
percentage (%)
Corresponding
Final
frequency
reference
Select main frequency
reference as final
frequency reference.
Para.
Select AI1 as main
frequency reference
setting channel.
F0-07 (units
position) = 0
+
10V
F0-03 = 2
Setting
GND
20.0%
80.0%