Loading...
3. Electrical Installation
- 30 -
3
Chapter 3 Electrical Installation
3.1 Typical System Connection
R
S
T
U
V
W
+24V
OP
DI
1
DI2
DI3
DI4
DI5
COM
+10V
AI2
GND
485+
485-
GND
AI1
T/A
T/B
T/C
FM
COM
DO1
CME
AO1
GND
A
B
Z
15
V
COM
PE
A1
B1
L1
L2
L3
M
PG
A
M
MDBUN
-
+
BR
- +
BR
VI
Jumper J7
Jumper J9
I
V
Forward run
F4
-00 =
1
Reverse run F4-01 =
2
Fault reset F
4-02 = 9
Reference 1
F4-03 = 11
Reference 2
F4-03 = 12
The DI5 supports a maximum
of 100 kHz pulse input.
1 to 5 kΩ
0 to 10 V
0 to 20 mA
Modbus-RTU
(
max.: 115200 bps
)
STP cable
Ground bar
Ground bar
MD38TX1
(optional)
J13
extension
port
0 V
J11 RJ45 for remote/ external
operating panel (keypad & display)
MD38
PGMD
(optional card
for closed-loop
operation)
J4 extension port
The drive of 18.5 to 75 kW
has built-in braking unit
The drive of 90 to 160 kW
requires an optional external
dynamic brake unit (MDBUN).
Encoder output pulses
Analog output
(voltage/current switchable)
0 to 10VDC/ 0 to 20mA
Pulse output: 0 to 100 kHz
Open-collector output:
10 to 24VDC/ 0 to 50mA
Open-collector output:
10 to 24VDC/ 0 to 50mA
Relay output:
250 VAC, between 10 mA and 3 A
30 VDC, between 10 mA and 1 A
FuseContactor
Breaker
( CANlink, CANopen,
PROFIBUS-DP also
supported)
Resolver also
supported. For
details,
see F1-
28

Table of Contents