6. Description of Parameters    
- 149 -
Function Code Parameter Name Setting Range Default
F7-05
LED display stop 
parameters
0000 to FFFF
7
6 5
4
3 2
1
0
Bus voltage (V)
DO state
AI1 voltage (V)
Count value
Frequency reference (Hz)
DI state
AI2 voltage (V)
AI3 voltage (V)
15
14 12 11
10
9 8
PLC stage
Pulse reference (kHz)
Length value
Reserved
13
Load speed
PID reference
Reserved
Reserved
If a parameter needs to be displayed during 
running, set corresponding bit to 1, and set F7-05 to 
hexadecimal equivalent.
1F
 ● Once the AC drive is re-powered on after power down, the display includes the 
selected parameters before power down by default.
 ● If parameters to be monitored cannot be found in F7-03, F7-04 and F7-05, view 
them in group U0.
 
■
View Parameters in Group U0
You can view parameter values by using operation panel, convenient for on-site commissioning, 
or from the host computer by means of communication (address: 0x7000-0x7044).
U0-00 to U0-31 are the monitoring parameters in the running and stop status dened by F7-03 
and F7-04.
Function Code Parameter Name Display Range
Group U0: Monitoring Parameters
U0-00
Running frequency
0.00 to 500.00 Hz 
U0-01
Frequency reference
0.00 to 500.0 Hz
U0-02
Bus voltage 0.0 to 3000.0 V
U0-03
Output voltage 0 to 1140 V
U0-04
Output current 0.00 to 655.35 A (AC drive power ≤ 55 kW)
0.0 to 6553.5 A (AC drive power > 55 kW)
U0-05
Output power 0 to 32767
U0-06
Output torque -200.0% to 200.0%