EasyManua.ls Logo

Inovance MD500 Series - dv;dt Reactor Installation

Inovance MD500 Series
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9. Technical Data
- 275 -
9
dv/dt Reactor Installation
Connect a dv/dt reactor on the output side to reduce large dv/dt, protecting the motor
winding from insulation breakdown, lowering motor temperature and extending the motor
service life and meanwhile reduce interference on surrounding devices.
Selection of the dv/dt reactor (Schaffner)
AC Drive Model dv/dt
Reactor
Model
Rated
Current
at 40°C
(A)
Rated
Motor
Power
(kW)
Rated
Inducance
(mH)
Power
Consum-
ption
(W)
I/O Terminal
Selection
Total
(kg)
MD500T18.5GB-
INT
RWK 305-
45-KL
45 18.5 0.131 60 KL - - 6.1
MD500T22GB-
INT
RWK 305-
45-KL
45 22 0.131 60 KL - - 6.1
MD500T30GB-
INT
RWK 305-
60-KL
60 30 0.098 65 KL - - 6.1
MD500T37GB-
INT
RWK 305-
72-KL
72 37 0.082 70 KL - - 6.1
MD500T45GB-
INT
RWK 305-
90-KL
90 45 0.065 75 KL - - 7.4
MD500T55GB-
INT
RWK 305-
110-KL
110 55 0.053 90 KL - - 8.2
MD500T75GB-
INT
RWK 305-
156-KS
156 75 0.038 120 - KS - 10.7
MD500T90G-INT RWK 305-
182-KS
182 90 0.032 140 - KS - 16
MD500T110G-
INT
RWK 305-
230-KS
230 110 0.026 180 - KS - 22
MD500T132G-
INT
RWK 305-
280-KS
280 132 0.021 220 - KS - 29
MD500T160G-
INT
RWK 305-
330-KS
330 160 0.018 240 - KS - 32
Mounting Dimensions (Unit: mm)
D
E
B
A
F
C
G
4-45A