6. Description of Parameters    
- 143 -
6.6.5  Motor Overheat Protection
Function Code Parameter Name Setting Range Default
F9-56
Type of motor temperature 
sensor
0: No temperature sensor
1: PT100
2: PT1000
0
F9-57
Motor overheat protection 
threshold
0°C to 200°C 110°C
F9-58
Motor overheat pre-warning 
threshold
0°C to 200°C 90°C
A motor temperature sensor can be connected to AI3 and PGND on extension I/O card. This 
input is used by the drive for motor overheat protection.
When input signal reaches the value set in F9-57, the AC drive detects Err25 and acts as 
selected in thousands position in F9-48. When input signal reaches the value set in F9-58, digital 
output terminal set for function 39 becomes on.
The drive supports both PT100 and PT1000. Make sure to set sensor type correctly. You can 
view motor temperature in U0-34.
6.6.6  Power Dip Ride-through
The power dip ride-through function ensures the system to run continuously at occurrence of 
momentary power loss. 
When an instantaneous power loss occurs, the AC drive compensates DC bus voltage reduction 
with real-time energy feedback by reducing output frequency, preventing the AC drive from 
stopping due to undervoltage.
 ● F9-59 = 1: It is applicable to large-inertia applications such as fan, water pump and centrifuge
 ● F9-59 = 2: It is applicable to the textile industry.
Figure 6-46 Power dip ride-through
Time (t)
Bus 
voltage
Output 
frequency
F9-61
F9-60
F9-62
Power dip ride-through
Time (t)